Feedthrough Capacitors FN751X
The FN751X AC Feedthrough Capacitors are designed to provide high insertion loss across a broad band of frequencies, from tens of kHz up to the GHz region. Their construction offers superior suppression performance compared to conventional two-wire capacitors. These capacitors are ideal for power line filtering in 110/240 VAC systems, enhancing system and information security. Key features include very low internal series inductance, high self-resonant frequency, self-healing dielectric, and high reliability. They are suitable for through-bulkhead mounting with anti-twist protection. Custom-specific or dual-versions are available upon request.
Features and Benefits
- Very low internal series inductance
- Very high self-resonant frequency
- Self-healing dielectric
- High quality and reliability
- Through-bulkhead mounting
- Anti-twist protection
- Custom-specific or dual-versions on request
Typical Applications
- Power line filter for 110/240 VAC power lines
- Increasing system and information security
- Power supplies
- Switching and cellular equipment
- Computer servers
- UPS power supplies
- Medical equipment
- Shielded rooms
Approvals & Compliances
- IEC/EN 60384-14 approval
- Class Y2 capacitor
- UL 94 V-2 or better flammability
- ENEC
Technical Specifications
| Model | Rated Current @ 60C [A] | Capacitance [nF] | DC Resistance [m] | Weight [g] | Max. Continuous Operating Voltage | High Potential Test Voltage | Insulation Resistance | Temperature Range | MTBF @ 60C/300 V | Operating Frequency |
| FN 7510-10-M3 | 10 | 2.2 | 0.8 | 15 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | <0.33 F, R >1500 M | -40C to +100C | >1,600,000 hours (<200 A) | DC to 60 Hz |
| FN 7511-10-M3 | 10 | 4.7 | 0.8 | 15 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | >0.33 F, >5000 s | -40C to +100C | >1,600,000 hours (<200 A) | DC to 60 Hz |
| FN 7510-16-M4 | 16 | 4.7 | 0.5 | 28 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | <0.33 F, R >1500 M | -40C to +100C | >1,600,000 hours (<200 A) | DC to 60 Hz |
| FN 7511-16-M4 | 16 | 10 | 0.52 | 28 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | >0.33 F, >5000 s | -40C to +100C | >1,600,000 hours (<200 A) | DC to 60 Hz |
| FN 7512-16-M4 | 16 | 47 | 0.62 | 33 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | >0.33 F, >5000 s | -40C to +100C | >1,600,000 hours (<200 A) | DC to 60 Hz |
| FN 7513-16-M4 | 16 | 100 | 0.58 | 65 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | >0.33 F, >5000 s | -40C to +100C | >1,600,000 hours (<200 A) | DC to 60 Hz |
| FN 7510-32-M4 | 32 | 4.7 | 0.52 | 28 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | <0.33 F, R >1500 M | -40C to +100C | >850,000 hours (200 A) | DC to 60 Hz |
| FN 7511-32-M4 | 32 | 10 | 0.52 | 28 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | >0.33 F, >5000 s | -40C to +100C | >850,000 hours (200 A) | DC to 60 Hz |
| FN 7512-32-M4 | 32 | 33 | 0.62 | 34 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | >0.33 F, >5000 s | -40C to +100C | >850,000 hours (200 A) | DC to 60 Hz |
| FN 7514-32-M4 | 32 | 100 | 0.58 | 65 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | >0.33 F, >5000 s | -40C to +100C | >850,000 hours (200 A) | DC to 60 Hz |
| FN 7512-63-M6 | 63 | 100 | 0.3 | 70 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | >0.33 F, >5000 s | -40C to +100C | >850,000 hours (200 A) | DC to 60 Hz |
| FN 7510-100-M8 | 100 | 47 | 0.23 | 100 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | <0.33 F, R >1500 M | -40C to +100C | >850,000 hours (200 A) | DC to 60 Hz |
| FN 7511-100-M8 | 100 | 100 | 0.23 | 100 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | >0.33 F, >5000 s | -40C to +100C | >850,000 hours (200 A) | DC to 60 Hz |
| FN 7511-200-M10 | 200 | 220 | 0.16 | 157 | 250 VAC (UL), 300 VAC (ENEC) | 3000 VDC for 2 sec | >0.33 F, >5000 s | -40C to +100C | >850,000 hours (200 A) | DC to 60 Hz |
2412091048_TE---Schaffner-FN7511-10-M3_C5742869.pdf
Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible